MEGA solid fuel boiler
MEGA solid fuel boiler
Fire-tube industrial heating boilers of long-term combustion with capacity from600 to1500 kW. The boiler furnace with a cast-iron grate ensures uniform and maximally efficient high-temperature combustion of fuel of various moisture levels. The working pressure of the boilers typeMEGA - to3 bar. It is possible to operate the boiler with torch-type burners and automatic ash removal system.
- Durability of the boiler - made of high-quality steel, 6-10 mm thick;
- Large furnace chamber;
- Reliable sealed doors with double insulation, which ensures safe operation and minimizes heat loss;
- High working pressure of the coolant;
- Possibility to adjust the air supply, depending on the type of fuel;
- Easy to maintain;
| Parameter | Unit. | Norm for the Altep Mega boiler | ||||
| Rated power of the boiler | kW | 600 | 800 | 1000 | 1200 | 1500 |
| Heat exchanger area | м2 | 49 | 60 | 75 | 86 | 98 |
| Firebox dimensions | ||||||
| depth | mm | 1380 | 1860 | 1860 | 2340 | 2820 |
| volume | м3 | 2,23 | 3,01 | 3,01 | 3,79 | 4,57 |
| Water capacity of the boiler | м3 | 1,9 | 2,3 | 2,8 | 3,4 | 4,0 |
| Weight of the boiler without water | kg | 4400 | 4850 | 5300 | 6200 | 7100 |
| Fuel gas temperature | °C | 100-180 | 100-180 | 100-180 | 100-180 | 100-180 |
| Recommended minimum water temperature | °C | 58 | 58 | 58 | 58 | 58 |
| Maximum water temperature | °C | 85 | 85 | 85 | 85 | 85 |
| Nominal operating water pressure | MPa | 0,30 (0,60*) | 0,30 (0,60*) | 0,30 (0,60*) | 0,30 (0,60*) | 0,30 (0,60*) |
| Electricity consumption, no more than | W | 1110 | 1110 | 1110 | 1660 | 1660 |
| Connecting (external) dimensions of the hog | mm | 450 | 450 | 500 | 600 | 600 |
| Diameter of mains water connections (DN) | mm | 125(FL) | 125(FL) | 125(FL) | 150(FL) | 150(FL) |
| Recommended chimney parameters | ||||||
| cross-sectional area | cm2 | 1590 | 1590 | 1970 | 2830 | 2830 |
| inner diameter | mm | 450 | 450 | 500 | 600 | 600 |
| height (minimum allowable) | м | 16 | 22 | 24 | 24 | 30 |
| Diameter of the pipe for the safety valve (DN) | mm | 2×50(FL) | 2×50(FL) | 2×65(FL) | 2×65(FL) | 2×65(FL) |
*Boilers with a nominal water pressure of 0.60 MPa are available on request.
Overall dimensions of the Altep MEGA boiler

| Parameter. | Unit of measurement |
Norm for the Altep Mega boiler | ||||
| Overall dimensions of the boiler | kW | 600 | 800 | 1000 | 1200 | 1500 |
| B | mm | 2430 | 2430 | 2430 | 2430 | 2430 |
| B1 | mm | 2080 | 2080 | 2080 | 2080 | 2080 |
| H | mm | 2670 | 2670 | 2870 | 2870 | 2870 |
| H1 | mm | 2430 | 2430 | 2630 | 2630 | 2630 |
| H2 | mm | 2082 | 2082 | 2263 | 2224 | 2224 |
| L | mm | 2950 | 3400 | 3400 | 3880 | 4330 |
| L1 | mm | 1910 | 2380 | 2380 | 2840 | 3290 |
| L2 | mm | 410 | 410 | 410 | 410 | 410 |
Fire-tube industrial heating boilers of the typeMEGA - long-burning combustion boilers operating in manual fuel loading and auto-feeding modes. They are installed in transportable and stationary boiler houses with closed heating systems. Power range: 600-1500 kW. The boiler heat exchanger is lined with chamotte stone.
The boiler is equipped with a cast-iron grate, large in area, which ensures uniform combustion of fuel of different humidity levels. The boilers operate at a high pressure level - up to 3 bar, which allows the equipment to be installed in heating systems with a high pressure level
of the heat carrier. The temperature in the boiler typeMEGAis regulated by a microprocessor in the form of a PID control unit.
To switch the boiler to the automatic fuel supply mode, it is necessary to additionally install a door for the pellet burner, the burner itself and the fuel hopper.
Олег
Сергей
07.04.2020
Александр
26.03.2020
You may be interested
Boiler ALTEP AGRO
- Power - 150 kW;
- Firebox volume - 1900 liters;
- Boiler weight without water - 2500 kg;