Solid fuel boiler AGRO

Customer Reviews: (1)
Boiler ALTEP AGRO Boiler ALTEP AGRO - [2] Boiler ALTEP AGRO - [3] Boiler ALTEP AGRO - [4]
Boiler ALTEP AGRO - [1]

Solid fuel boiler AGRO

Customer Reviews: (1)

AGRO- is a fire-tube industrial solid fuel boiler with manual fuel loading, which can be installed in both stationary and transportable boiler houses with a closed heating system.

  • The efficiency is 86%;
  • steel thickness 6-8 mm;
  • large furnace chamber;
  • PID control unit is installed;
  • ease of operation.
Fuel
Straw
Metal thickness
up to 8 mm
Environmental friendliness
Warranty
3 years
Power
150-600 kW
EFFICIENCY
from 86%
specifications
Dimensions
Description
Reviews (1)
Parameter Unit of measurement Norm for the Altep AGRO boiler
Rated power output kW 150
Fuel - Straw, moisture content not exceeding 20 %
Heat exchanger area м2 22
EFFICIENCY %</notranslate 86
Firebox dimensions
depth mm 1450
diameter mm 1300
volume dm3 1900
Water capacity of the boiler л 1500
Boiler weight without water kg 2500
The required flue gas flow Pa. 60-80
Flue gas temperature at the boiler outlet °C 100-180
Recommended minimum water temperature °C 58
Maximum water temperature °C 85
Nominal (maximum operating) water pressure MPa 0,30
Test water pressure, max. MPa 0,50
Electricity consumption W 270
Connecting (outer diameter) dimensions of the hog mm 298
Diameter of the direct and return water pipes (DN) mm 80 (FL)
Recommended chimney parameters
cross-sectional area cm2 702
inner diameter mm 300
height (minimum allowable) м 10
Diameter of the connections for the safety valve (DN) mm 50 (FL)

Overall dimensions of the Altep AGRO boiler

Parameter Unit of measurement Norm for Altep AGRO boilers
Overall dimensions of the boiler kW 150
B mm 2170
B1 mm 1840
H mm 2220
H1 mm 2100
H2 mm 1802
H3 mm 380
L mm 2400
L1 mm 1860
L2 mm 340

Boiler typeAGRO has a large firebox designed to load one or more small straw bundles and burn them.

The temperature is regulated by a microprocessor in the form of an automation unit. It is able to stabilize the water temperature by smoothly reducing and increasing the number of revolutions of the discharge fan, which blows the boiler. The convection part of the boiler consists of two rows of flame tubes.

1 reviews on Solid fuel boiler AGRO

Андрей
02.07.2020

Котел показав себе дуже чудово у роботі. Якщо є чим його топити, котел рекомендую!

02.07.2020
Дякуємо за Ваш відгук!

You may be interested

Have a question? Book a consultation